define(`TITLE', `M-Bus Master, Part 3 (Water)')
|
|
define(`DATE', `2013-09-10')
|
|
define(`CONTENT', `
|
|
Now, also the water meter talks to me.
|
|
|
|
<a href="http://a385e-5.de/wp-content/uploads/2013/09/Wasserzaehler.jpg"><img src="http://a385e-5.de/wp-content/uploads/2013/09/Wasserzaehler-225x300.jpg" alt="Wasserzaehler" width="225" height="300" class="alignnone size-medium wp-image-173" /></a>
|
|
|
|
(Note the thin grey cable, that'`s the M-Bus cable.)
|
|
|
|
And, after a small modification of the circuit I can talk to water meter and electric power meter connected in parallel to the master.
|
|
|
|
|
|
|
|
<blockquote>
|
|
<a href="http://a385e-5.de/wp-content/uploads/2013/09/laser-drucker_005120.jpg"><img src="http://a385e-5.de/wp-content/uploads/2013/09/laser-drucker_005120-209x300.jpg" alt="laser-drucker_005120" width="209" height="300" class="alignnone size-medium wp-image-192" /></a>
|
|
|
|
IC2 was already added in the last step, since the output of the analog circuit and the requirements of the MCU didn'`t match concerning their logical polarity.
|
|
|
|
Now, T3 (BS108) and R9 (2k2) have been added to disable the receive path while data is transmitted.
|
|
</blockquote>
|
|
|
|
|
|
Responding the <code>REQ_UD2</code> command, the water meter sends this telegram (address 0x30 has been assigned to it first):
|
|
|
|
<code>
|
|
so 10 5b 30 8b 16
|
|
success
|
|
SO RESP: 68 46 46 68 08 30 72 45 71 43 00 24 23 25 07 02 00 00 00 0C
|
|
13 51 84 00 00 8C 10 13 00 00 00 00 0B 3B 00 00 00 0B 26 62 06 00 02
|
|
5A CC 00 04 6D 17 16 A9 19 7C 13 00 00 00 00 FC 10 13 00 00 00 00 72
|
|
6C 00 00 42 EC 7E BF 1C 35 16
|
|
</code>
|
|
|
|
A closer look, consulting the <a href="http://www.m-bus.com/mbusdoc/md8.php" title="M-Bus documentation" target="_blank">M-Bus documentation</a> reveals the meaning:
|
|
|
|
[table]Octet(s), Field, Meaning
|
|
<code>68 46 46 68</code>, Preamble with length,
|
|
<code>08</code>, C field,
|
|
<code>30</code>, A field (address),
|
|
<code>72</code>, CI field, variable data response
|
|
|
|
<code>45 71 43 00</code>, Ident. No.,
|
|
<code>24 23</code>, Manufacturer , HYD = Hydrometer GmbH
|
|
<code>25</code>, Version,
|
|
<code>07</code>, Medium, Water
|
|
<code>02</code>, Access No.,
|
|
<code>00</code>, Status,
|
|
<code>00 00</code>, Signature,
|
|
|
|
<code>0C</code>, DIF, 8 digit BCD
|
|
<code>13</code>, VIF, Volume; 10^(3-6)m^3
|
|
<code>51 84 00 00</code>, Value, 8.451m^3
|
|
<code>8C</code>, DIF, ext; 8 digit BCD
|
|
<code>10</code>, DIFE, minimum value
|
|
<code>13</code>, VIF, Volume; 10^(3-6)m^3
|
|
<code>00 00 00 00</code>, Value, 0
|
|
<code>0B</code>, DIF, 6 digit BCD
|
|
<code>3B</code>, VIF, Volume flow; 10^(3-6)m^3/h
|
|
<code>00 00 00</code>, Value, 0
|
|
<code>0B</code>, DIF, 6 digit BCD
|
|
<code>26</code>, VIF, Operating time; hours
|
|
<code>62 06 00</code>, Value, 662h = 27.6d
|
|
<code>02</code>, DIF, 16bit integer
|
|
<code>5A</code>, VIF, Flow Temperature; 10^(2-3)°C
|
|
<code>CC 00</code>, Value, 20.4°C
|
|
<code>04</code>, DIF, 32bit integer
|
|
<code>6D</code>, VIF, Time Point; time&date
|
|
<code>17 16 A9 19</code>, Value,
|
|
<code>7C</code>, DIF, LSB; value during error state; 8 digit BCD
|
|
<code>13</code>, VIF, Volume; 10^(3-6)m^3
|
|
<code>00 00 00 00</code>, Value, 0
|
|
<code>FC</code>, DIF, ext; LSB; value during error state; 8 digit BCD
|
|
<code>10</code>, DIFE, tariff 1
|
|
<code>13</code>, VIF, Volume; 10^(3-6)m^3
|
|
<code>00 00 00 00</code>, Value, 0
|
|
<code>72</code>, DIF, LSB; value during error state; 16bit integer
|
|
<code>6C</code>, VIF, Time Point; date
|
|
<code>00 00</code>, Value, 0
|
|
<code>42</code>, DIF, LSB; 16bit integer
|
|
<code>EC</code>, VIF, ext; Time Point; date
|
|
<code>7E</code>, VIFE, ??
|
|
<code>BF 1C</code>, Value,
|
|
|
|
<code>35</code>, Checksum,
|
|
<code>16</code>, Stopbyte,
|
|
[/table]
|
|
|
|
Decoding of the time&date type is done like this:
|
|
<pre>
|
|
if (t_data)
|
|
{
|
|
if (t_data_size == 4) // Type F = Compound CP32: Date and Time
|
|
{
|
|
if ((t_data[0] & 0x80) == 0) // Time valid ?
|
|
{
|
|
t->tm_min = t_data[0] & 0x3F;
|
|
t->tm_hour = t_data[1] & 0x1F;
|
|
t->tm_mday = t_data[2] & 0x1F;
|
|
t->tm_mon = (t_data[3] & 0x0F) - 1;
|
|
t->tm_year = ((t_data[2] & 0xE0) >> 5) |
|
|
((t_data[3] & 0xF0) >> 1);
|
|
t->tm_isdst = (t_data[1] & 0x80) ? 1 : 0; // day saving time
|
|
}
|
|
}
|
|
else if (t_data_size == 2) // Type G: Compound CP16: Date
|
|
{
|
|
t->tm_mday = t_data[0] & 0x1F;
|
|
t->tm_mon = (t_data[1] & 0x0F) - 1;
|
|
t->tm_year = ((t_data[0] & 0xE0) >> 5) |
|
|
((t_data[1] & 0xF0) >> 1);
|
|
}
|
|
}
|
|
</pre>
|
|
(Found on github in the libmbus repo.)
|
|
|
|
') |